LVDBS_II
hybryd_lvdbs_topologia_en
hybryd_lvdbs_jednostka

LVDBS

LVDBS low voltage battery and control system
Description

Low Voltage Distributed Battery System enables to supply emergency and evacuation lighting luminaries. The system consists of the LVDBS unit (which contains control, monitoring and power supply electronic systems with batteries) and luminaries connected to it.

System is designed in accordance with EN 1838, EN 50171, EN 50172 and EN 62485-2.

FEATURES

  • User-friendly menu
  • State signalisation from each line
  • Small system size
  • SELV network
  • Possible configuration of each line in the lighting mode, door holders (electromagnet) and signalling (horn or flash)
  • Possible creation of fire signalisation scenarios for respective lines
  • Automatic performance of tests in accordance with EN 50172
  • Possibly of connecting circuits controlling the system operation
  • 4 inputs controlled by potential-free contacts
  • Possibly of connecting the informative and signalling system
  • 3 outputs (system deactivation signalisation, battery operation signalisation, failure signalisation)
  • Possibility of the system history preview and loading history to the external USB memory
  • Possibility of generating reports and saving them in the external USB memory
  • Ethernet socket
  • Cooperation with BMS (Building Management System)

Emergency operation time is one, two or three hours* (*3h is a special order). Hermetic maintenace-free batteries with the lifespan of 10 years are used.

It is dedicated to operation:

  • at input voltage of 230V AC
  • at output voltage of 24V DC

During normal operation, the output voltage is obtained directly from the power supply, powered from the power grid, which additionally charges the batteries. During a power failure, the system goes into emergency mode and the 24V DC output voltage is obtained from batteries.

This type of system is intended for small buildings or where the replacement of autonomous luminaire batteries would generate high costs (e.g due to the mounting high of luminaries), and the use of HVCBS (high voltage central battery system) system would not be profitable.

TECHNICAL DATA

Power supply 230V AC
Connection power 500VA
Power load on one circuit *   75 W
Number of circuits 4
Output voltage 24V DC
Buffer voltage level 27,2V
Ambient temperature 15°C - 25°C
Emergency operation time 1h / 2h / 3h
Processor Intel 2x1,46GHz
Battery capacity 20Ah / 40Ah / 65Ah
Weight 15kg / 27kg / 60kg **
Dimensions 400 x 500 x 21mm

* - measured on LVDBS unit terminals; ** - LVDBS cabinet + cabinet with 65Ah batteries

LVDBS UNIT

LVDBS units are equipped with a microprocessor controller with display and press button membrane panel. The controller is responsible for controlling the system operation and for communication with Control Unit or computer set through TCP/IP connector ETHERNET. Communication between cabinets enables you to view system results and states by means of the main unit.

COMMUNICATION

The system may consist of 32 units connected through EIA/TIA-485 connector but operating independently. A communication line uses 2 standards led in a screen, e.g HTKSHekw 1x2x0,8. Communication with luminaires supplied with the voltage of 24V DC takes place through lines power supply (2x2,5mm2). Address modules are used for individual luminaries control. LVDBS can also be expanded with mode, information on errors, tests and operating status are displayed on a clear, modern LCD display.